10 June 2010

More Photos of the Interchutz 2010 at Lepzig...

Steam powered fire engine

Fire Extinguishers can be very interesting...







09 June 2010

Currently i am at the Interschutz 2010, the largest International Exhibition on Fire Prevention & Fire Fighting Industries.

Foam Monitor with Pressurized Foam Tank

A Malaysian Exhibitor doing preparation works


An antique extinguisher on display



A modern Cartridge operated type portable fire extinguisher on display


A military fire truck

A fire truck with pumping and hose equipment


An early fire car, i think it is a Fiat



Display on early portable fire extinguishers


A beauty with an early extinguisher


A remote control Monitor system, it moves like a robotic arm

Manual Water & Foam Monitors

An Ambulance truck

My Malaysian & Singaporean friends


A rescue superbike, with an extinguisher on it, can you see where it is located?

This is the main hof, where we hae our dinner, not many choices though, but the price is reasonable.

01 February 2010

The training i mentioned in my last post was done on the 16 Jan 2010.  Instead of a few colleagues, it turned out to be more than 10 of them.  One of our subsidiary company staffs also joins in.  It is not the numbers that worried me, but it is the fact that some of them are experienced engineers.  I delivered the classroom part as per my earlier planning, but had to skip most of the slides considering the time limitation.
The practical part i asked one of my colleague to handle and it all went on well.

Most of the trainees had a chance to operate the fire extinguisher and tried to extinguish a small fire.
This photo shows a trainee trying to kill the fire.

Alow me to comment a bit on this photo.

First, look at his foot steps, he was standing with right foot forward, and he is holding the discharge nozzle with his right hand.  Usually, this is not the best way to approch a fire because it is harder to balance the weight of the extinguisher cylinder.  It also appears to me that he is not fully confident, therefore he reserve his left leg at the back, prepared to make a rereat in case of uncontrolled situation.

Now, look at how he hold the discharge hose.  He is holding it at the nozzle tip like holding a pencil.  This method usually results in a sharper angle of discharge on the fire base, as you can see, the angle is about 45 degree.  In this case, because the fuel is liquid, the powder discharge may splash the liquid fuel out of the tray and ended up on the grass, and the grass will start burning, and he will have to deal with more spots of fire.  And, that was exactly what happened, but i did not record it in photo.

So, what is the problem with aiming at that angle?
No, there is nothing wrong, as long as the fire is extinguished, peacefully and quickly.
In a small fire like this one, we cannot really see the difference because there is practically a lot more powder than required to kill the fire, but if the fire gets bigger and bigger, we will need to put every gram of powder into action, to extinguisher the fire, ..... otherwise, the fire will extinguish us.

In my next post, i will try to elaborate what it means and how to put the extinguishing agent to action.

14 January 2010

Fire Extingusher Training

Early this week, i was requested to conduct a training to a few new colleagues who have just joined my company not long ago, on basic knowledge of fire extinguishers.  After some communications with this and that person, i got it arranged in the coming saturday.

It will be a 90 minutes session, of which the first 60 minutes will be a classroom lecture with a slide presentation and followed by 30 minutes of practical operating a portable fire extinguisher.

I spend some time getting the slides ready and got another colleague to prepare some extinguishers, petrol and a tray.  I have not delivered such training for some time, so need to flip back my old notes to recall the key words correctly.

10 December 2009

How Many Units of Fire Extinguisher to Use?

Most often this is the question i got, "How Many Units Of Fire Extinguisher Do I Need To Provide In My Office", or Factory, or whatever it is.

Let's not go into the theory first. Neither do i try to be technical.
Let's just look around.  If those people out there have placed the extinguishers in their premises, and they are operating with a legal status, then they must be doing something right.  Or close to right.  Right??

I see most commercial shop lots, say, 30' X 80',  will most likely provide 2 units of 9 kg ABC Powder Portable Fire Extinguisher. Maybe 1 unit in the front and another in the middle or back.
Then, if there is a upper floor office, i notice another unit placed near the main entrance and another unit either in the office or at the pantry or near the wash rooms.

Now, let's see what the Legal Requirement Says.
According to the Malaysian Building By-Law, the correct Malaysian Standards, or The Code Of Practice to follow, is the Malaysian Standards, MS1539 : Part 3 : 2003.
This document is the Specification For Portable Fire Extinguishers - Part 3.
Focusing on Selection And Installation - and it is a Code Of Practice, make sure you refer to the current version, which is the (First Revision), or any later version if any.

Many aspects are explained in very detail in this document.

Among others, i think will give us a simple understanding, are as the following:

a) Extinguisher Spacing

The fire extinguishers must be located such that, you can get to it without having to walk more than 20 meter.



b) Extinguisher Hanging Height

If the fire extinguisher is heavier than 4kg, (which i think most cases are) it must be hang such that the handle is about 1 meter from the floor
This is spelled out in MS1539 : Part 3 : 2003, clause 7.2


c) Calculation According To Floor Space

Since year 2002, Fire Extinguishers are approved by the Fire Brigade according to their capability to kill fire, and we are talking about how big a fire can be killed, or extinguished, if you don't prefer to kill.

  Before this, not much emphasis on this "Size Of Fire Killed thing, or, technically refered to as "Fire Rating", but rather the size, in terms of kg of the fire extinguisher matters more.

The calculation goes like this : if you have a specific floor space, say, 1000 meter square.
Then, the required "Fire Rating" is calculated as, 1000 X 0.065.
So, what we get is, 65A of Fire Rating Required for that space.

Then what is 65A???

To know what this 65A means, and to translate it into number of fire extinguishers, we need to know the rating of each fire extinguisher.  Now, take a look at the fire extinguisher near you, is there any?
Read the label printed on the fire extinguisher body, and you should see somehere printed the Fire Rating. Read the A rating number, maybe you will see something like, 27A/144B.

Now, assuming it is 27A.  Now, the number of fire extinguisher required is : 65A / 27A
... and we should get an answer of 2.41
round it up, it comes to 3 units of Fire Extinguisher.


What i have shared here, is just some basic points, of course there are many-many more things to consider when making provision for fie safety.  Anybody interested to know further, please puchase a copy of the Code from SIRIM for reference.

11 November 2009

How To Choose A Fire Extinguisher Contractor or Supplier

Basically, a Contractor or Supplier dealing with Fire Protection Equipment Supply and/or service, shall be registered with Bomba.  The criteria for the registration are:

a) A Registered Company with ROC

Verification documents : Borang 9 : Sijil Pendaftaran Syarikat,
                                     Form 24 : Sijil Pengesahan Modal Di benar dan Modal Berbayar,
                                     Form 49 : Sijil Pengesahan Maklumat Pengarah, Pengurus dan Setiausaha Syarikat
                                     M & A : Memorandum dan Artikel Perbadanan Syarikat

b) Licenced with Local Government, eg. : Lesen Perniagaan MBSJ
c) If using e-perolehan, register with Ministry of Finance, eg.: Sijil Pendaftaran Kementrian Kewangan

If the contractor is providing service and maintenance service for fire extinguishers, then the company shall have a complete set of servicing facilities such as:

a)  powder filling machine,
b) CO2 filling machine,
c) leakage test equipment,
d) valve tightening machine,
e) clamping device and
f) any dedicated tools, as specified by manufacturers
g) appropriate waste disposal

The company shall also have competent qualified technical personnel relevant to the job, operating based on documented standard operating procedures on maintenance and servicing of portable fire extinguishers in compliance with the relevant Code of Practice, using replacement parts and procedures prescribed by hte manufacturers.

Some companies, voluntarily, get their company certified by a third party, such as SIRIM.
At the moment, this third party certification is not mandatory, but i believe later it will be mandatory by law.
This is because the Code of Practice has been gazetted by the government and published as a Malaysian Standards, back in 2004.

07 November 2009

Bomba Certificate for Fire Extinguisher

I used to get questions from my friends who wants to know how to apply for Bomba Certificate for fire extinguishers.  They were told that this certificate is required by the local town council to complete their application for business licence.  To abtain this certificate, the premise owner has to purchase Fire Extinguisher which are Certified by SIRIM, Approved by BOMBA and meets the Code of Practise, in terms of size, type and location of installation.  Application to the nearest Balai Bomba has to be made using Borang APA 1, APA 2 & APA 3. with payment.  Upon approval, normally 2 to 3 days, a certificate called H13 and a receipt is issued.  The first copy of H13 is to be paste onto the fire extinguisher body.  Make sure does not obstruct the originl label on the extinguisher body, especially the operating instructions.  The second copy is to be kept for future reference.  Sometimes the local authority requires the receipt as prove of approval, sometime they require the second copy to be submitted together with the business licence application or renewal.